CPSC, Honeywell Sensing and Controls Announce Recall of Thermal Switches
Product Description
These "Snap Action" thermal switches were sold under the model number 2450A, 2455RA, or 2455RM. They have model numbers and date codes stamped on the sensing surface or end cap. Following are those model numbers and date codes that are part of the corrective action: Model Number Date Codes Part of Corrective Action 2455RA and 2450A Z0412, Z0413, Z0414, Z0415, Z0416, Z0417, Z0418, Z0419, Z0420, Z0421, Z0427, Z0429, Z0430, Z0431,Z0432, Z0434, Z0435, Z0436, Z0437 2455RM Z0421, Z0427, Z0429, Z0430, Z0431, Z0432, Z0434, Z0435, Z0436, Z0437
Reason for Recall
When these switches are used in fire or HVAC dampers and heat detectors, they could fail to operate, causing the damper not to close or causing the heat detector not to alarm, if there is a fire.
Remedy
Honeywell Sensing and Controls will provide a free replacement switch.
Details
- Recalling Firm
- Honeywell Sensing and Controls, of Freeport, Ill.
- Units Affected
- About 113,500, including about 12,200 that were installed in buildings
Frequently Asked Questions
What product was recalled? ▼
Why was this product recalled? ▼
What should consumers do? ▼
Which agency issued this recall? ▼
Related Recalls
Vive Health Recalls Adult Portable Bed Rails Due to Risk of Serious Injury or Death from Entrapment and Asphyxiation; V…
Ningbo Shenyu Medical Equipment Co., Ltd., of China · 2026-02-19
Beloems Adult Portable Bed Rails Recalled Due to Risk of Serious Injury or Death from Entrapment and Asphyxiation; Viol…
Leioujiapin Technology Co., Ltd. dba Beloems, of China · 2026-02-12
Fortemotus Direct Adult Portable Bed Rails Recalled Due to Risk of Serious Injury or Death from Entrapment and Asphyxia…
Guangzhou Kezhinuo Maoyi Youxian Gongsi, dba Fortemotus Direct US, of China · 2026-02-12
Airova Recalls Aroeve Air Purifiers Due to Fire and Burn Hazards
· 2026-02-09
Aterian Recalls PurSteam Elite Travel Steamers and Mighty Lil Steamers Due to Risk of Serious Burn Injury
· 2026-02-05