ANSUL Recalls Fire Extinguisher that Could Fail to Operate

Reported: November 13, 2006 Initiated: November 13, 2006 #07507

Product Description

The recall involves K-GUARD® Wet Chemical, FLAG FIRE® KITCHEN ONE® Wet Chemical, FLAG FIRE® Water and SENTRY® Water Fire Extinguishers manufactured and shipped between May 2003 and September 9, 2005. The recall program involves pick-up tube replacements in the following extinguishers: Brand Model Part Number(s) K-GUARD® Wet Chemical K01-1 430849 (UL) 430850 (ULC) K01-2 432843 (UL) 432848 (ULC) SENTRY® Water W02-1 430847 (English) 430848 (Spanish/English) FLAG FIRE® KITCHEN ONE® Wet Chemical KS-6000 552055 (UL) 552500 (ULC) FLAG FIRE® Water PWS-25G 552050 (UL) 552501 (ULC) Model numbers can be found on the fire extinguisher labels. Affected models meet the following criteria: The year 2004 or 2005 is stamped on the hanger hook attachment on the shell. For 2003 models, information on specific serial numbers included in the recall can be found at www.ansul.com for the K-GUARD Wet Chemical and SENTRY Water extinguishers, or at www.pyrochem.com for the FLAG FIRE and KITCHEN ONE Wet Chemical extinguishers. Contact the firm to determine if your extinguisher is included in this replacement program.

Reason for Recall

If the fire extinguisher is dropped horizontally from a height of approximately 2 to 3 feet, the pick-up tube could crack at the threads between the pick-up tube adaptor and the stainless steel tube. If a pick-up tube is cracked, the extinguisher can fail to discharge properly when activated, which can put users at risk during a fire.

Remedy

Pick-up tube replacements will be performed during routine annual maintenance. The pick-up tube assembly is inside the extinguisher and cannot be visually inspected without de-pressurizing and disassembling the extinguisher. This work should only be done by an authorized ANSUL® distributor. Owners concerned about an extinguisher prior to the scheduled maintenance, due to signs of physical damage such as dents or scratches, should contact their authorized ANSUL® distributor to request a free replacement.

Frequently Asked Questions

What product was recalled?
The recall involves K-GUARD® Wet Chemical, FLAG FIRE® KITCHEN ONE® Wet Chemical, FLAG FIRE® Water and SENTRY® Water Fire Extinguishers manufactured and shipped between May 2003 and September 9, 2005. The recall program involves pick-up tube replacements in the following extinguishers: Brand Model Part Number(s) K-GUARD® Wet Chemical K01-1 430849 (UL) 430850 (ULC) K01-2 432843 (UL) 432848 (ULC) SENTRY® Water W02-1 430847 (English) 430848 (Spanish/English) FLAG FIRE® KITCHEN ONE® Wet Chemical KS-6000 552055 (UL) 552500 (ULC) FLAG FIRE® Water PWS-25G 552050 (UL) 552501 (ULC) Model numbers can be found on the fire extinguisher labels. Affected models meet the following criteria: The year 2004 or 2005 is stamped on the hanger hook attachment on the shell. For 2003 models, information on specific serial numbers included in the recall can be found at www.ansul.com for the K-GUARD Wet Chemical and SENTRY Water extinguishers, or at www.pyrochem.com for the FLAG FIRE and KITCHEN ONE Wet Chemical extinguishers. Contact the firm to determine if your extinguisher is included in this replacement program.. Recalled by Ansul Incorporated, of Marinette, Wis.. Units affected: About 154,000.
Why was this product recalled?
If the fire extinguisher is dropped horizontally from a height of approximately 2 to 3 feet, the pick-up tube could crack at the threads between the pick-up tube adaptor and the stainless steel tube. If a pick-up tube is cracked, the extinguisher can fail to discharge properly when activated, which can put users at risk during a fire.
What should consumers do?
Pick-up tube replacements will be performed during routine annual maintenance. The pick-up tube assembly is inside the extinguisher and cannot be visually inspected without de-pressurizing and disassembling the extinguisher. This work should only be done by an authorized ANSUL® distributor. Owners concerned about an extinguisher prior to the scheduled maintenance, due to signs of physical damage such as dents or scratches, should contact their authorized ANSUL® distributor to request a free replacement.
Which agency issued this recall?
This recall was issued by the CPSC on November 13, 2006. Severity: Moderate. Recall number: 07507.