Gamewell-FCI Recalls Fire Alarm Panels Due to Failure to Alert of a Fire, Smoke or CO
Product Description
This recall is for the ILI-MB-E3 and ILI-S-E3 Gamewell-FCI fire alarm panels in commercial buildings. This issue is limited to a specific configuration of Signaling Line Circuit (SLC) devices. To occur, the SLC must include at least two of the following detectors in any combination: Acclimate, 4-Warn, Photo/CO and iFAAST. The issue would occur only if the detectors are addressed within the same FlashScan polling group. Detectors installed in a different combination are not affected.
Reason for Recall
When configured in a certain way, the panels can become non-responsive and connected detectors in the area can fail to detect and respond to an alarm.
Remedy
Consumers should immediately contact the distributor to obtain the free repair, a firmware upgrade.
Details
- Recalling Firm
- Gamewell-FCI of Northford, Conn.
- Units Affected
- About 1,000
Frequently Asked Questions
What product was recalled? ▼
Why was this product recalled? ▼
What should consumers do? ▼
Which agency issued this recall? ▼
Related Recalls
Convenience Kits 1. 25GA Convenience Kit - FNX VS0644.25-FNX 2. 25GA Convenience Kit - FXX VS0644.25-FXX 3.2…
Vortex Surgical Inc. · 2026-02-11
COULTER DxH Diluent, REF 628017 COULTER DxH ECO Diluent REF C67250 For use as an isotonic buffered diluent in conju…
Beckman Coulter, Inc. · 2026-02-11
Product Name: Single Use 3-Lumen Sphincterotome V Model/Catalog Number: KD-V411M-1520 Product Description: These inst…
Olympus Corporation of the Americas · 2026-02-11
Product Name: Disposable Triple Lumen Sphincterotome Model/Catalog Number: KD-401Q-0330 Product Description: These in…
Olympus Corporation of the Americas · 2026-02-11
Product Name: Lumipulse pTau 217 Plasma Controls Model/Catalog Number: 81558 Software Version: Not Applicable Produc…
Fujirebio Diagnostics, Inc. · 2026-02-11